Cables and Construction Products Regulations
 
 

Scope of the CPR

The scope of the Regulation is to ensure the free circulation of construction products in the European Union, establishing harmonised rules on how to express the performance of construction products in order to minimize the risks to persons or property, reducing fires danger.

What is a Construction product: Art. 2 clause 1 of the CPR

Construction product means any product or kit which is produced and placed on the market for incorporation in a permanent manner in construction works or parts thereof and the performance of which has an effect on the performance of the construction works with respect to the basic requirements for construction works;

 
 

Economic Operators Involved According to the CPR

Manufactures are involved as they have to place on the market cables conform to the requirements of the Regulation.Distributors are involved as they must when making a cable available on the market, and shall act with due care in relation to the requirements of this Regulation and pass downstream the foreseen documentation (e.g. DoP).

Classification of fire performances

Cables can be classified in 7 classes of Reaction to Fire, identified by the letters from “F” to “A” and the subscript “ca” (cable) according to their increasing level of performance.

 
 

CABLES WITH REACTION TO FIRE REQUIREMENTS

The cables are classified in 7 classes of Reaction to Fire, identified by the letters from “F” to “A” and the subscript “ca” (cable) according to their increasing performance. 

In addition to this main classification, the European authorities have also regulated the use of the following additional parameters

 

SMOKE


FLAMING DROPLETS


ACIDITY


 

In Italy the CEI UNEL 35016 standard for electrical cables provides only the CPR classes of reaction to fire:

 
 

-B2ca-s1a, d1, a1;
-Cca-s1b, d1, a1;
-Cca-s3, d1, a3;
-Eca.


 
 
 

CPR CABLES

 
CAVI NON CPR
NEW CABLES complying with the CPR standard
Fire Classification
N07V-K
FS17 450/750 V
Cca-s3,d1,a3
FG7R 0,6/1 kV
FG16R16 0,6/1 kV
Cca-s3,d1,a3
FG7OR 0,6/1 kV
FG16OR16 0,6/1 kV
Cca-s3,d1,a3
N07G9-K
FG17 450/750 V
Cca-s1b,d1,a1
FG7M1 0,6/1 kV
FG16M16 0,6/1 kV
Cca-s1b,d1,a1
FG7OM1 0,6/1 kV
FG16OM16 0,6/1 kV
Cca-s1b,d1,a1
FG10M1 0,6/1 kV
FG18M16 0,6/1 kV
B2ca-s1a,d1,a1
FG10OM1 0,6/1 kV
FG18OM16 0,6/1 kV
B2ca-s1a,d1,a1
FG7OH2R 0,6/1 kV
FG16OH2R16 0,6/1 kV
Cca-s3,d1,a3
FG7OH2M1 0,6/1 kV
FG16OH2M16 0,6/1 kV
Cca-s1b,d1,a1
FTG10M1 0,6/1 kV
FTG18M16 0,6/1 kV
B2ca-s1a,d1,a1
FTG10M1 0,6/1 kV
FTG18OM16 0,6/1 kV
B2ca-s1a,d1,a1
U/RG7R-0.6/1 kV
U/RG16R16-0,6/1 kV
Cca-s3,d1,a3
U/RG7OR-0.6/1 kV
U/RG7OR-0.6/1 kV
Cca-s3,d0,a3