H07Z-K

Reaction to Fire CPR: Eca

Single core power cable with flexible conductor insulated with rubber insulation Type EI 5, flame retardant on a single vertical cable test, having low emission of smoke and corrosive gases when exposed to fire.

.
.
.
 
 

H07Z-K Single-core flexible conductor      Class Eca (CPR)

Rated voltage: Uo/U  450/750 V

Standards: : CEI EN 50525-1,CEI EN 50525-3-41; CEI EN IEC 60228; CEI EN IEC 60332-1-2 ; CEI EN 50267-2-1; CEI EN 61034-2, EN 50575:2014+A1:2016.

Regulation Construction Products: 305/2011 EU.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 CEI EN IEC 60228.

Insulation: polyolefin based cross-linked material of type EI5, having low emission of smoke and tcorrosive gases when exposed to fire.

Colour: blue, black, brown, grey, green/yellow, red, white, turquoise, violet, orange, pink.

Marking: continuous marking on the insulation: on one side « ICEL  H07Z-K  IEMMEQU <HAR> Ecogamma  Eca»,
on opposite side « nominal cross-section, year of production, MADE IN ITALY ».

Minimum installation and handling temperature: - 5 °C

Maximum operating temperature: 90 °C on the conductor.

Minimum usage temperature: - 20 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 250 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radii: 4 times the overall diameter if the cable diameter is lower than 8 mm; 5 times if between 8 and 12 mm; 6 times if over 12 mm.

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.

Guidance for Use: for installation where high presence of people is foreseen and a low level of emission of smoke and corrosive gases are required in case of fire or burning. Installation in surface mounted or embedded conduits, or similar closed systems; suitable for fixed protected installation in, or on, lighting or control gear for voltages up to 1000 V a.c. or, up to 750 V d.c. to earth.
Unsuitable: for installation in bunches, for outdoor use, direct or indirect burring in earth, in damp premises, directly under plaster.

Further instructions and guidance for use are given in the EN 50565 and CEI 20-40 standards.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.

 
.