H03V2V2-F

Flexible power cables PVC insulated, under a light PVC sheath, with a maximum continuous operating temperature of 90 °C.

.
.
 
 

H03V2V2-F Multi-core sheathed round flexible cable 

Rated voltage: Uo/U 300/300 V

Standards: EN 50525-1, EN 50525-2-11, EN IEC 60332-1-2, EN IEC 60228.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper,class 5 (EN IEC 60228)

Insulation: PVC of type TI3.

Insulation colours:
two cores: blue-brown;
three cores: green/yellow-blue-brown or brown-black-grey;
four cores: green/yellow-brown-black-grey or blue-brown-black-grey;

Sheath: PVC type TM3.Colour: black or white; if explicitly requested, and for agreed quantities, may be supplied in other single colours.

Marking: continuous marking on one side of the sheath: « ICEL H03V2V2-F IEMMEQU<HAR> ECOGAMMA »,
on the opposed side « nominal cross-section, year of production, MADE IN ITALY ».

Maximum operating temperature: 90 °C on the conductor; the temperature to which the cable is exposed may be due to high ambient temperature of the installation and/or by the heat generated by the appliances in which the cables are installed.

Minimum installation and handling temperature: + 5 °C

Minimum usage temperature: - 10 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 150 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radii: 
For free movements 5 times the overall diameter;
For fixed installations 3 times the greatest overall dimension;
For repeated wrappings 7 times the greatest overall dimension.

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section.

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.
For the sections up to 0,75 mm²:
section (mm²) 0,5 - 0,75
current (A)         3   -   6

Guidance for Use: For use in domestic appliances in which the cable is going to operate at high temperatures; unsuitable for outdoor installations, in industrial or agricultural buildings or for non-domestic portable tools.

Further instructions and guidance for use are given in the EN 50565 standard.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.

* For present agreements it is not allowed to mark the Harmonised cables and their labels with the marking of special national Standards. The mark “ECOGAMMA” indicates the use of lead free compounds

 
.