N2XH J/O Single-core Dca

Reaction to Fire CPR: Dca-s1,d2,a1

LS0H sheathed cables with improved properties in the event of fire, with solid or stranded conductor for fixed wiring.

.
.
 
 
 
.
.
 
Number and Nominal cross sectional area
Thickness of insulation specified value
Thickness of sheath specified value
Outer Diameter approx.
Weight approx.
Maximum resistance
of conductors
at 20 °C
n x mm²
mm
mm
mm
g/m
ohm/km
1 x 1,5 RE
0,8
1,8
6,7
14
12,1
1 x 2,5 RE
0,8
1,8
7,1
26
7,41
1 x 4 RE
1,0
1,8
8,0
38
4,61
1 x 6 RE
1,0
1,8
8,5
58
3,08
1 x 10 RE
1,0
1,8
9,3
95
1,83
1 x 16 RM
1,0
1,8
10,8
155
1,15
1 x 25 RM
1,2
1,8
12,3
240
0,727
1 x 35 RM
1,2
1,8
13,3
335
0,524
1 x 50 RM
1,4
1,8
14,8
480
0,387
1 x 70 RM
1,4
1,8
16,6
670
0,268
1 x 95 RM
1,6
1,8
18,8
910
0,193
1 x 120 RM
1,6
1,8
20,2
1150
0,153
1 x 150 RM
1,8
1,8
22,1
1430
0,124
1 x 185 RM
2,0
1,8
24,2
1775
0,0991
1 x 240 RM
2,2
1,8
27,1
2300
0,0754
1 x 300 RM
2,4
1,9
29,9
2870
0,0601
1 x 400 RM
2,6
2,0
34,0
3830
0,0470
1 x 500 RM
2,8
2,1
38,0
4800
0,0366
 

N2XH-J/O Single-core sheathed round cable

Rated voltage: Uo/U  0,6/1 kV

Standards: DIN VDE 0276-604; VDE 0295 cl.1 or cl.2 ; EN 50267-2-1 (DIN VDE 0482-267-2-1) EN 50267-2-2 (DIN VDE 0482-267-2-2); EN IEC 61034-1 (DIN VDE 0482-1034-1)EN IEC 61034-2 (DIN VDE 0482-1034-2); EN IEC 60332-1 serie (DIN VDE 0482-332-1); EN IEC 60332-3-24 (Kat.C) (DIN VDE 0482-332-3-24 (Kat.C)), EN 50575:2014+A1:2016.

European directives:L.V.D. 2014/35/UE - 2011/65/EC and 2015/863/EU (RoHS)

Regulation Construction Products: 
305/2011 EU.

Conductor: annealed plain copper, solid (RE) class 1 or stranded (RM) class 2 VDE 0295 (EN IEC 60228).

Insulation: Cross-linked Polyethylene type 2XI1.

Colours of the cores: green/yellow (N2XH-J) or black (N2XH-O);

Sheath: Thermoplastic halogen-free compound type HM4.
Colour of the sheath: black

Marking: continuous marking on the sheath: “ I.C.E.L. N2XH-J or N2XH-O nominal cross section 0,6/1 kV <VDE> 0276 production date “.
Progressive meter marking.

Maximum operating temperature:
90 °C on the conductor.

Maximum short circuit temperature:  250 °C on the conductor (for maximum 5 seconds).

Operating temperature in fixed installation min/max:  -30 °C / +90 °C

Handling temperature min/max: -5 °C / +50 °C

Minimum internal bending radius: 15 times the greatest overall dimension.

Maximum tensile stress: 5 kg/mm² of the conductor cross section

Guidance for Use: To be installed in buildings or industrial plants where many people and goods are present. As these  cables don't develop corrosive and halogen gases in the event of fire, and also the smoke generation is limited and not opaque, the damage caused in case of fire is limited. They can be installed on, in and under the wall-surface, in dry, humid and wet locations, indoors or outdoors when protected from solar radiation, but not directly in ground and water.