H05V-K

Reaction to Fire CPR: Eca

Single-core non-sheathed power cable with flexible conductor for internal wiring.

.
.
.
 
 

H05V-K Single-core flexible conductor up to 1 mm²

Rated voltage: Uo/U  300/500 V 

Standards: EN 50525-1, EN 50525-2-31, EN IEC 60332-1-2, EN IEC 60228, EN 50575:2014+A1:2016.

Regulation Construction Products: 
305/2011 EU.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: flexible annealed plain copper class 5 (EN IEC 60228).

Insulation: PVC of type TI1.

Insulation Colour:
blue, dark blue, light blue, black, brown, grey, green/yellow, red, white, turquoise, violet, orange, pink, green, yellow and all the bicolour combinations of these colours;

* Marking: continuous marking on the insulation: on one side « ICEL H05V-K IEMMEQU <HAR> ECOGAMMA  Eca »,
on the opposed side « nominal cross section, year of production, MADE IN ITALY ».

Minimum installation and handling temperature: + 5 °C

Maximum operating temperature: 70 °C on the conductor.

Minimum usage temperature: - 10 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 160 °C on the conductor (for maximum 5 seconds).

Minimum internal bending radii: 4 times the overall diameter.

Maximum tensile stress: 1,5 kg/mm² of the conductor cross section.

Current carrying capacity: see EN 50565-1 standard and CEI-UNEL 35024.
For cross-sections up to 1 mm²:
cross-section (mm²) 0,5 - 0,75 - 1
current (A)                   3    -   6    -   10

Guidance for Use: 
fixed protected installation inside appliances and in, or on, lighting fittings; suitable for installation in surface mounted or embedded conduits, only for signalling or control circuits;
Not suitable for: direct or indirect burial, laying outdoors or in wet environments, unprotected laying, or laying under plaster.

Further instructions and guidance for use are given in the EN 50565 standard.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.

*For present agreements it is not allowed to mark the Harmonised cables and their labels with the marking of special national Standards.
The mark ECOGAMMA indicates the use of lead free compounds.