RG7OR–0,6/1 kV

Multicore power cables, G7 rubber insulated, PVC sheathed, with stranded conductors for fixed installations. Resistant to fire propagation with reduced emission of corrosive gases under fire conditions.

.
 
 
.
.
 
 

 Tab. CEI-UNEL 35376

Number and nominal cross-sectional area of conductors
Minimum
number of
conductor wires
Thickness
of insulation
specified value
Indicative
core
diameter
Thickness
of sheath
specified value
Maximum
overall
diameter
Indicative
cable
weight
Maximum
resistance
of conductors
at 20 °C
mm²
n
mm
mm
mm
mm
g/m
ohm/km
2 x 10
6
0,7
5,2
1,8
16,6
440
1,83
2 x 16
6
0,7
6,1
1,8
18,6
600
1,15
2 x 25
6
0,9
7,8
1,8
22,1
850
0,727
2 x 35
6
0,9
8,8
1,8
24,6
1130
0,524
2 x 50
6
1,0
10,2
1,8
28,1
1480
0,387
2 x 70
12
1,1
12,0
1,8
31,7
2040
0,268
2 x 95
15
1,1
13,7
2,0
35,9
2700
0,193
2 x 120
18
1,2
15,4
2,1
39,8
3350
0,153
2 x 150
18
1,4
17,2
2,2
44,2
4100
0,124
3 G 10
6
0,7
5,2
1,8
17,5
530
1,83
3 G 16
6
0,7
6,1
1,8
19,7
740
1,15
3 G 25
6
0,9
7,8
1,8
23,4
1130
0,727
3 G 35
6
0,9
8,8
1,8
26,2
1450
0,524
3 G 50
6
1,0
10,2
1,8
29,9
1950
0,387
3 G 70
12
1,1
12,0
1,9
34,1
2650
0,268
3 G 95
15
1,1
13,7
2,0
38,3
3480
0,193
3 G 120
18
1,2
15,4
2,1
42,5
4380
0,153
3 G 150
18
1,4
17,2
2,3
47,4
5350
0,124
3 G 185
30
1,6
19,3
2,4
52,9
6700
0,0991
3 G 240
34
1,7
21,9
2,6
59,3
8700
0,0754
3 G 300
34
1,8
24,3
2,7
65,2
10900
0,0601
3 G 400
53
2,0
27,4
3,0
74,6
13600
0,047
4 G 10
6
0,7
5,2
1,8
19,0
630
1,83
4 G 16
6
0,7
6,1
1,8
21,5
900
1,15
4 G 25
6
0,9
7,8
1,8
25,7
1480
0,727
3x35 +25
6
0,9
8,8
1,8
28,0
1700
0,524 / 0,727
3x50 +25
6
1,0 / 0,9
10,2
1,8
31,1
2000
0,387 / 0,727
3x70 +35
12 / 6
1,1 / 0,9
12,0
1,9
35,4
2800
0,268 / 0,524
3x95 +50
15 / 6
1,1 / 1,0
13,7
2,1
40,3
4000
0,193 / 0,387
3x120 +70
18 / 12
1,2 / 1,1
15,4
2,2
44,9
5200
0,153 / 0,268
3x150 +95
18 / 15
1,4 /1,1
17,2
2,4
50,3
6300
0,124 / 0,193
3x185 +95
30 / 15
1,6 / 1,1
19,3
2,5
54,9
7600
0,0991 / 0,193
3x240 +150
34 / 18
1,7 / 1,4
21,9
2,7
62,8
10000
0,0754 / 0,124
3x300 +150
34 / 18
1,8 / 1,4
24,3
2,9
67,8
12000
0,0601 / 0,124
3x400 +240
53 / 34
2,0 / 1,7
27,4
3,2
78,8
15900
0,0470 / 0,0754
5 G 10
6
0,7
5,2
1,8
20,6
780
1,83
5 G 16
6
0,7
6,1
1,8
23,4
1100
1,15
5 G 25
6
0,9
7,8
1,8
28,0
1750
0,727
5 G 35
6
0,9
8,8
1,8
31,5
2100
0,524
5 G 50
6
1,0
10,2
2,0
36,6
2900
0,387
If explicitly requested, and for agreed quantities, a version of the cables without the protective conductor (green/yellow) can be supplied.
 
 

RG7OR–0,6/1 kV Multicore cable, stranded conductors over 6 mm²

Nominal voltage
: Uo/U 0,6/1 kV.

Maximum voltage: 1,8 kV d.c. also to earth

Standards: CEI 20-13, CEI 20-11; CEI EN e IEC 60228 (CEI 20-29); CEI 20-22 II, CEI EN 60332-1-2 (CEI 20- 35), CEI EN 50267-2-1 (CEI 20-37/2-1); HD 605-A1.

European directives: 2014/35/UE (LVD)  - 2011/65/EC and 2015/863/EU (RoHS).

Conductor: stranded plain annealed copper class 2 CEI EN IEC 60228.

Insulation: hard ethylene propylene rubber (HEPR) compound, of type G7, with reduced emission of halogen (corrosive gases) under fire conditions.

Colour of the cores:
Two cores: blue – brown.
Three cores: blue – brown – green/yellow   or   brown – black – grey.
Four cores: brown – black – grey – green/yellow   or   blue – brown – black – grey.
Five cores: blue – brown – black – grey – green/yellow or blue – brown – black – grey – black.

Sheath: PVC of type Rz with reduced emission of halogen (corrosive gases) under fire conditions.
Resistance to UV exposure, measured according to the CENELEC standard HD 605, for a sure outside non protected to sun light installation.
Colour:  light grey.

Marking: continuous marking on the sheath: « ICEL or LOMBARDA RG7OR-0,6/1 kV nominal cross section CEI 20-22 II IEMMEQU ECOGAMMA production date Made in Italy », with under the sheath the IEMMEQU thread.
Progressive meter marking.

Minimum installation and handling temperature: + 0 °C

Maximum operating temperature: 90 °C on the conductor.

Minimum usage temperature: - 15 °C only if the cable is not subjected to shocks, vibrations, movements or other mechanical stresses. If the cable is operated at a constant current and so is not subjected to expansions and contractions due to the conductor temperature variations, it is possible to be used even at lower temperatures.

Maximum short circuit temperature: 250 °C on the conductor (for maximum 5 seconds).

Minimum permissible bending radii: 4 times the cable overall diameter.

Maximum pulling force during laying: 5 kg/mm² of the conductor cross section.

Current carrying capacity: see CEI-UNEL 35024, 35026.

Guide to Use: for internal installations, also in wet locations and for external installations; for installation in surface mounted or on metallic structures; direct laying in earth permitted.

See also the guide to use standard CEI 20-67.

These cables are to be used only for electrical power transmission and to be installed only by skilled personal.