LS0H sheathed cables with improved properties in the event of fire, with solid or stranded conductor for fixed wiring.
Number and Nominal cross sectional area |
Thickness of insulation specified value |
Thickness of sheath specified value |
Outer Diameter approx. |
Weight approx. |
Maximum resistance of conductors at 20 °C |
---|---|---|---|---|---|
n x mm² |
mm |
mm |
mm |
kg/km |
ohm/km |
1 x 1,5 RE |
0,8 |
1,8 |
6,7 |
14 |
12,1 |
1 x 2,5 RE |
0,8 |
1,8 |
7,1 |
26 |
7,41 |
1 x 4 RE |
1,0 |
1,8 |
8,0 |
38 |
4,61 |
1 x 6 RE |
1,0 |
1,8 |
8,5 |
58 |
3,08 |
1 x 10 RE |
1,0 |
1,8 |
9,3 |
95 |
1,83 |
1 x 16 RM |
1,0 |
1,8 |
10,8 |
155 |
1,15 |
1 x 25 RM |
1,2 |
1,8 |
12,3 |
240 |
0,727 |
1 x 35 RM |
1,2 |
1,8 |
13,3 |
335 |
0,524 |
1 x 50 RM |
1,4 |
1,8 |
14,8 |
480 |
0,387 |
1 x 70 RM |
1,4 |
1,8 |
16,6 |
670 |
0,268 |
1 x 95 RM |
1,6 |
1,8 |
18,8 |
910 |
0,193 |
1 x 120 RM |
1,6 |
1,8 |
20,2 |
1150 |
0,153 |
1 x 150 RM |
1,8 |
1,8 |
22,1 |
1430 |
0,124 |
1 x 185 RM |
2,0 |
1,8 |
24,2 |
1775 |
0,0991 |
1 x 240 RM |
2,2 |
1,8 |
27,1 |
2300 |
0,0754 |
1 x 300 RM |
2,4 |
1,9 |
29,9 |
2870 |
0,0601 |
1 x 400 RM |
2,6 |
2,0 |
34,0 |
3830 |
0,0470 |
1 x 500 RM |
2,8 |
2,1 |
38,0 |
4800 |
0,0366 |
N2XH-J/O Single-core sheathed round cable
Rated voltage: Uo/U 0,6/1 kV
Standards: DIN VDE 0276-604; VDE 0295 cl.1 or cl.2 ; EN 50267-2-1 (DIN VDE 0482-267-2-1) EN 50267-2-2 (DIN VDE 0482-267-2-2); EN IEC 61034-1 (DIN VDE 0482-1034-1)EN IEC 61034-2 (DIN VDE 0482-1034-2); EN IEC 60332-1 serie (DIN VDE 0482-332-1); EN IEC 60332-3-24 (Kat.C) (DIN VDE 0482-332-3-24 (Kat.C)), EN 50575:2014+A1:2016.
Regulation Construction Products: 305/2011 EU.
European directives:L.V.D. 2014/35/UE - 2011/65/EC and 2015/863/EU (RoHS)
Conductor: annealed plain copper, solid (RE) class 1 or stranded (RM) class 2 VDE 0295 (EN IEC 60228).
Insulation: Cross-linked Polyethylene type 2XI1.
Colours of the core: green/yellow (N2XH-J) or black (N2XH-O);
Sheath: Thermoplastic halogen-free compound type HM4.
Colour of the sheath: black
Marking: continuous marking on the sheath: “ I.C.E.L. N2XH-J or N2XH-O nominal cross section 0,6/1 kV <VDE> 0276 production date “.
Progressive meter marking.
Maximum operating temperature: 90 °C on the conductor.
Maximum short circuit temperature: 250 °C on the conductor (for maximum 5 seconds).
Operating temperature in fixed installation min/max: -30 °C / +90 °C
Handling temperature min/max: -5 °C / +50 °C
Minimum internal bending radius: 15 times the greatest overall dimension.
Maximum tensile stress: 5 kg/mm² of the conductor cross section
Guidance for Use: To be installed in buildings or industrial plants where many people and goods are present. As these cables don't develop corrosive and halogen gases in the event of fire, and also the smoke generation is limited and not opaque, the damage caused in case of fire is limited. They can be installed on, in and under the wall-surface, in dry, humid and wet locations, indoors or outdoors when protected from solar radiation, but not directly in ground and water.